A Case Study on Anti-islanding Protection of Distributed Generation Using Autoground: Hydro-Québec Smart Grid Demonstration
Author:
EPRI
Year:
2013
Abstract:

This case study presents results of Hydro-Québec’s construction and testing of an anti-islanding approach, referred to as an autoground. The premise of the approach is to allow the distributed generation system time to detect the islanding situation. This is done using a pas­sive approach up until the moment just prior to reclosing of the substation breaker, at which point the autoground momentarily short circuits the feeder, forcing any remaining distributed generation resources to discon­nect based on line protection.
The autoground approach was proposed by Hydro-Québec in the context of the IEEE 1547.8 recommended prac­tices working group.
The authors address considerations of implementing autoground technology, focusing on its incorporation with an existing distribution protection philosophy, construction in partnership with manu­facturers, and establishing open dialog with distribution generation proponents.